9353 2008
80A 2P ATYS-gM M AUTO C/O SWITCH
R21,697.15
Supplier:
Pack Size: 1
ATyS g M automatic changeover switches
The ATyS g M switch monitors the supply from both mains and from generator. On mains failure, the switch provides an output to start generator and once the generator voltage reaches the correct level, switches over to the generator supply until mains is restored, causing the switch to change back to the mains supply and stop the generator.
Potentiometers for:
- Nominal voltage configuration
- Voltage and frequency threshold configuration
- Operating cycle configuration
DIP- switches for:
- 50 or 60Hz, single or 3-phase
- Delay in O position during I-O transfer cycles
LED indication of:
- Supply source availability, automatic mode, fault
External command inputs:
- Manual change of supply from emergency to main source
- Remote test on-load (or priority change)
- 1NO output relay for generator start/stop command
AC-31 B 415V (A) | 80A |
NUMBER OF POLES | 2 |
SUPPLY VOLTAGE | 230 VAC |
DESCRIPTION | ATyS g M automatic changeover switches |
DIMENSIONS (MM) | (H) 245 x (W) 235 x (D) 74 |