50-0012
CTB 31.35 500/5A CT cl 1
R305.86
Supplier:
Pack Size: 1
Current transformers
The CTB range with "cage clamp ®" termination (uneffected by vibration and shock) offers a higher maximum operating voltage (Um < 1,2 kV) and increased isolation test voltage (6 kV Ueff, 1 min., 50 Hz) as well as increased ambient temperature range (-5 °C < T < +50 °C).
General specifications:
- Isolation class: E
- Nominal rated frequency: 50 Hz
- Maximum operating voltage Um: 1.2 kV
- Isolation test voltage: 6 kV, Ueff, 50 Hz, 1 minute
- Nominal thermal current Icth: 1.2 x In (continuous)
- Thermal nominal short-time current Ith: 60 x In, 1 seccond
- UL-Certificate Number - 20100426-E336996, DIN EN 61869 part 1+2
Current transformers with screwless connection technology
CTB 31.35 current transformers (5A secondary class 1)
MODEL | CTB 31.35 |
RATIO | 500/5A |
ROUND CONDUCTOR (Ø) | 25.7 mm |
PRIMARY BAR CONDUCTOR | 30 X 10 / 25 X 12/ 20 x 20 mm |
DESCRIPTION | Standard current transformer |
CLASS | 1 |
VA | 10 |
DIMENSIONS (MM) | (H) 81 x (W) 60 x (D) 52 |